Typical test system 3
(1) The IEEE 9-node power system shown in the following figure:
2. Component parameters
(1) Line parameters
Line number (km) ro (_/km) XO (_/km) Bo (1/_km)
L1 25 0.131 0.4 2.98 x 10-6
L2 50 0.131 0.4 2.98 x 10-6
L3 45 0.105 0.393 3 3.04 x 10-6
L4 30 0.131 0.4 2.98 x 10-6
L5 35 0.105 0.393 3 3.04 x 10-6
L6 20.131 0.4 2.98 x 10-6
(2) Transformer parameters
Transformer Capacity (MVA) Variable Ratio Pk (kW) P 0 (kW) Uk% i0%
T1 50 121/10.5 250 55 10.5 1.5
T2 80 121/10.5 410 98 10.5 1.5
T3 50 121/10.5 250 55 10.5 1.5
(3) Node parameters
Node Name Type P (MW) Q (MVar) Voltage Phase Angle
1 PQ 3518
2 PQ 3016
3 PQ 4020
4 PQ 2512
5 PQ 2010
6 PQ 156
7 PV 40 1.05
8 PV 45 1.05
9 Balance Point 1.05 0.0